Sureseal 2000 (SS2K) Flameproof EEx d & Increased Safety EEx e Cable Gland

CMP Sureseal 2000 Dual Certified Flameproof (Type 'd') and Increased Safety (Type 'e') Cable Gland for all types of Unarmoured Cables. This Cable Gland provides a Flameproof seal on the cable inner sheath (or outer sheath of single sheathed cable) and a secondary environmental seal on the cable outer sheath. Suitable for use Zone 1, Zone 2, Zone 21 and Zone 22 Hazardous Areas, this Cable Gland design affords extra stability and superior resistance to cable pull out. Type SS2KPB available for unarmoured cables with lead sheath.

  Technical Data
   Type
   SS2K (SS2KPB for Lead Sheathed Cables)
   Design Specification
   BS 6121:Part 1:1989, EN 50262
   ATEX Certification Detail
   SIRA02ATEX1057X
   ATEX Code of Protection Category
   ATEX Ex II 2 GD EEx d IIC & EEx e II, Equipment Zone 1, Zone 2, Zone 21, & Zone 22 - Gas Groups IIA, IIB, IIC
   EN Compliance Standards
   EN 50014:1997, EN 50018:2000, EN 50019:2000, EN 50281-1-1:1998, IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-1-1
   GOST Ex Certificate
   2002.C256
   GOST Code of Protection Category
   Ex d IIC U / Ex e II U
   GOST Compliance Standards
   GOST P 51330.8-99, GOST P 51330.1-99, GOST P 51330.13-99, GOST P 51330.0-99
   GOST GGTN Permit
   PPC04-6783
   GOST Certificate of Conformity
   5318857
   Lloyds Approval No.
   01/00172
   DNV Approval No.
   E-6157
   ABS Approval No.
   01-LD 234401-PDA
   Continuous Operating Temperature
   -60℃ to +130℃
   Ingress Protection Rating
   IP67, IP68, IP66
   Ingress Protection Document
   5046 C549K
   Deluge Protection Compliance
   DTS01 : 91
   Deluge Protection Document
   5046 C549K-D
   Standard Cable Gland Material
   Brass
   Alternative Cable Gland Material
   Nickel Plated Brass, Aluminium, Stainless Steel
   Seal Material
   CMP SOLO LSF
   Cable Type
   Unarmoured
   Sealing Technique
   CMP Unique Displacement Seal Concept
   Sealing Area(s)
   Outer Sheath
   Accessories
   Adaptor/Reducer, Entry Thread Seal, Serrated Washer, Locknut, Shroud, Earth Tag

Integral Entry Thread Seal Option Available (for this option pre-fix gland type with 'R' e.g.25RSS2K)

  Additional Information
   Special Conditions For Safe Use 02ATEX1057X
Open Link
 
CMP SS2K Type Cable Gland photograph
 
RSS2K Version Pictured SS2K Version Illustrated
 
 
CMP SS2K Type Cable Gland line diagram
 

Cable Gland Selection Table

     
Gland Size Standard Entry Threads 'C' Minimum Thread Length 'D' Cable Dia 'A' / 'B' Across Corners Dia 'E' Max Ordering Reference (Metric)
Metric NPT PG Min Max
16 16 1/2" PG11 15 3.1 8.6 24.4 16SS2K
20/16 20 1/2" PG11 15 3.1 8.6 24.4 20/16SS2K
20S 20 1/2" PG13.5 15 6.1 11.6 26.5 20SSS2K
20 20 1/2" PG16 15 6.5 13.9 30.0 20SS2K
25 25 3/4" PG21 15 11.1 19.9 39.9 25SS2K
32 32 1" PG29 15 17.0 26.2 45.5 32SS2K
40 40 1-1/4" PG36 15 22.0 32.1 55.4 40SS2K
50S 50 1-1/2" PG36 15 29.5 38.1 61.0 50SSS2K
50 50 2" PG42 15 35.6 44.0 66.5 50SS2K
63S 63 2" PG48 15 40.1 49.9 77.6 63SSS2K
63 63 2-1/2" - 15 47.2 55.9 83.2 63SS2K
75S 75 2-1/2" - 15 52.8 61.9 88.7 75SSS2K
75 75 3" - 15 59.1 67.9 94.2 75SS2K
90 90 3" - 15 66.6 79.3 120.7 90SS2K
100 100 3-1/2" - 15 76.0 91.0 136.0 100SS2K
115 115 4" - 15 86.0 98.0 148.0 115SS2K
130 130 4-1/2" - 15 97.0 115.0 162.0 130SS2K
All dimensions are in millimetres unless otherwise stated
 
 