Brass indoor and outdoor cable gland for all types of lead covered,
braided or steel tape armour (S.T.A) cables, providing environmental
seal on both the cable inner and outer sheaths. The gland also provides
mechanical cable retention and electrical continuity via wire braid
or tape armour termination and bonding of lead sheath.
Technical Data
Type
E2X/Z
Design Specification
BS 6121:Part 1:1989, EN 50262
Continuous Operating Temperature
-60℃ to +150℃
Ingress Protection Rating
IP66
Standard Cable Gland Material
Brass
Alternative Cable Gland Material
Nickel Plated Brass, Aluminium
Seal Material
CMP Formulated Evoprene
Cable Type
Lead Sheathed & Wire Braid Armour, Lead
Sheathed & Steel Tape Armour (LC/STA)
CMP SOLO Option with LSF Seals and LSF Shrouds also
available Integral Entry Thread Seal Option available (for this
option pre-fix gland type with 'R', e.g.25RE2X/Z)
RE2X/Z version colour
coded with red ferrule for ease of identification
Cable Gland Selection Table
Gland Size
Standard Entry Threads 'C'
Minimum Thread Length 'D'
Cable Dia 'A'
Cable Dia 'B'
Braid Thickness Max
Across Corners Dia 'E' Max
Ordering Reference (Metric)
PVC Shroud Ref.
Metric
NPT
PG
Min
Max
Min
Max
20S
20
1/2"
PG13.5
10
6.1
11.6
9.5
15.9
0.8
26.6
20SE1X/Z
PVC04
20
20
1/2"
PG16
10
6.5
13.9
12.5
20.9
0.9
33.3
20E1X/Z
PVC06
25
25
3/4"
PG21
10
11.1
19.9
17.0
26.2
1.2
40.5
25E1X/Z
PVC09
32
32
1"
PG29
10
17.0
26.2
22.9
33.9
1.4
51.0
32E1X/Z
PVC11
40
40
1-1/4"
PG36
15
22.0
32.1
26.0
40.4
1.4
61.0
40E1X/Z
PVC15
50S
50
1-1/2"
PG36
15
29.5
38.1
35.0
46.7
1.4
66.5
50SE1X/Z
PVC18
50
50
2"
PG42
15
35.6
44.0
38.0
53.1
1.4
77.7
50E1X/Z
PVC21
63S
63
2"
PG48
15
40.1
49.9
45.6
59.4
1.5
83.2
63SE1X/Z
PVC23
63
63
2-1/2"
-
15
47.2
55.9
54.6
65.9
1.5
88.7
63E1X/Z
PVC25
75S
75
2-1/2"
-
15
52.8
61.9
57.0
72.1
1.5
101.6
75SE1X/Z
PVC28
75
75
3"
-
15
59.1
67.9
60.4
78.5
1.5
111.1
75E1X/Z
PVC30
90
90
3"
-
15
66.6
79.3
69.2
90.4
1.6
128.6
90E1X/Z
PVC32