E2FW Cable Gland
CMP Products Cable Gland Main E2FW Data
CMP产品E2FW电缆密封接头详细信息介绍

 
E2FW Flameproof EEx d & Increased Safety EEx e Cable Gland

CMP Type E2FW Dual Certified Flameproof (Type 'd') and Increased Safety (Type 'e') indoor and outdoor cable gland for use in Zone 1, Zone 2, Zone 21 and Zone 22 Hazardous Areas with all types of Lead Covered SWA cable providing a Flameproof seal on the cable inner sheath and an environmental seal on the cable outer sheath. The cable gland also provides mechanical cable retention and electrical continuity via armour wire termination & earth bonding of Lead Sheath.

  Technical Data
   Type
   E2FW
   Design Specification
   BS 6121:Part 1:1989, EN 50262
   ATEX Certification Detail
   SIRA01ATEX3287X
   ATEX Code of Protection Category
   ATEX Ex II 2 GD EEx d IIC & EEx e II, Equipment Zone 1, Zone 2, Zone 21, & Zone 22 - Gas Groups IIA, IIB, IIC
   EN Compliance Standards
   EN 50014:1997, EN 50018:2000, EN 50019:2000, EN 50281-1-1:1998, IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-1-1
   Australian Approval No.
   AUS Ex764
   Australian Code of Protection Category
   Ex d II Class I Zone 1
   Australian Compliance Standards
   AS2236-1994, AS1939-1990, AS2380.2/1991, AS1828-1985, AS2380.1/1989
   GOST Ex Certificate
   2002.C256
   GOST Code of Protection Category
   Ex d IIC U / Ex e II U
   GOST Compliance Standards
   GOST P 51330.13-99, GOST P 51330.1-99, GOST P 51330.0-99, GOST P 51330.8-99
   GOST GGTN Permit
   PPC04-6783
   GOST Certificate of Conformity
   5318857
   Lloyds Approval No.
   01/00172
   DNV Approval No.
   E-6157
   ABS Approval No.
   01-LD 234401-PDA
   Continuous Operating Temperature
   -60℃ to +130℃
   Ingress Protection Rating
   IP66
   Standard Cable Gland Material
   Brass
   Alternative Cable Gland Material
   Aluminium, Nickel Plated Brass
   Seal Material
   CMP SOLO LSF
   Cable Type
   Lead Sheathed & Single Wire Armour (LC/SWA)
   Armour Clamping
   Two Part Armour Lock
   Sealing Technique
   CMP Unique Displacement Seal Concept
   Sealing Area(s)
   Inner & Outer Sheath
   Accessories
   Adaptor/Reducer, Entry Thread Seal, Earth Tag, Shroud, Serrated Washer, Locknut

CMP SOLO Option with LSF Shrouds also available.
Integral Entry Thread Seal Option available (for this option pre-fix gland type with 'R', e.g.25RE2FW)


  Additional Information
   Special Conditions For Safe Use 01ATEX1286X, 01ATEX3287X
Open Link
 
CMP E2FW Type Cable Gland photograph
   
 
CMP E2FW Type Cable Gland line diagram
 

Cable Gland Selection Table

 
Gland Size Standard Entry Threads 'C' Minimum Thread Length 'D' Cable Dia 'A' Cable Dia 'B' Armour Wire Dia Across Corners Dia 'E' Max Ordering Reference (Metric) PVC Shroud Ref.
Metric NPT PG Min Max Min Max
20S 20 1/2" PG13.5 15 6.1 11.6 9.5 15.9 0.9/1.25 26.6 20SE2FW PVC04
20 20 1/2" PG16 15 6.5 13.9 12.5 20.9 0.9/1.25 33.3 20E2FW PVC06
25 25 3/4" PG21 15 11.1 19.9 17.0 26.2 1.25/1.6 40.5 25E2FW PVC09
32 32 1" PG29 15 17.0 26.2 22.9 33.9 1.6/2.0 51.0 32E2FW PVC11
40 40 1-1/4" PG36 15 22.0 32.1 26.0 40.4 1.6/2.0 61.0 40E2FW PVC15
50S 50 1-1/2" PG36 15 29.5 38.1 35.0 46.7 2.0/2.5 66.5 50SE2FW PVC18
50 50 2" PG42 15 35.6 44.0 38.0 53.1 2.0/2.5 78.6 50E2FW PVC21
63S 63 2" PG48 15 40.1 49.9 45.6 59.4 2.5 83.2 63SE2FW PVC23
63 63 2-1/2" - 15 47.2 55.9 54.6 65.9 2.5 89.0 63E2FW PVC25
75S 75 2-1/2" - 15 52.8 61.9 57.0 72.1 2.5 101.6 75SE2FW PVC28
75 75 3" - 15 59.1 67.9 60.4 78.5 2.5/3.15 111.1 75E2FW PVC30
90 90 3" - 15 66.6 79.3 69.2 90.4 3.15 128.6 90E2FW PVC32
All dimensions are in millimetres unless otherwise stated
 
 

More information related to these cable glands is available from CMP Products main website.

More info on CMP Products E2FW cable gland