CWe Cable Gland
CMP Products Cable Gland Main CWe Data
CMP产品CWe电缆密封接头详细信息介绍

 
CWe Increased Safety EEx e Cable Gland

CMP Type CWe Increased Safety (Type 'e') indoor and outdoor cable gland for use in Zone 1, Zone 2, Zone 21 and Zone 22 Hazardous Areas with all types of SWA cable providing environmental seal on the cable outer sheath. The cable gland also provides mechanical cable retention and earth continuity via armour wire termination. Suitable for use in conjunction with Increased Safety (type 'e') apparatus or EEx de equipment which has an increased safety terminal chamber.

  Technical Data
   Type
   CWe
   Design Specification
   BS 6121:Part 1:1989, EN 50262
   ATEX Certification Detail
   SIRA01ATEX3287X
   ATEX Code of Protection Category
   ATEX Ex II 2 GD EEx e II, Equipment Zone 1, Zone 2, Zone 21, & Zone 22 - Gas Groups IIA, IIB, IIC
   EN Compliance Standards
   EN 50014:1997, EN 50019:2000, EN 50281-1-1:1998, IEC 60079-0, IEC 60079-7, IEC 61241-1-1
   Australian Approval No.
   ANZEx 03.3000-0
   Australian Code of Protection Category
   DIP A21 IP66, Ex e II
   Australian Compliance Standards
   IEC 60079-0:1998, IEC 60079-7:2001, IEC 61241-1-1:1999, IEC 60529:1989
   GOST Ex Certificate
   2002.C256
   GOST Code of Protection Category
   Ex e II U
   GOST Compliance Standards
   GOST P 51330.13-99, GOST P 51330.8-99, GOST P 51330.0-99
   GOST GGTN Permit
   PPC04-6783
   GOST Certificate of Conformity
   5318857
   Lloyds Approval No.
   01/00172
   ABS Approval No.
   01-LD 234401-PDA
   Continuous Operating Temperature
   -60℃ to +130℃
   Ingress Protection Rating
   IP66
   Standard Cable Gland Material
   Brass
   Alternative Cable Gland Material
   Aluminium, Nickel Plated Brass
   Seal Material
   CMP SOLO LSF
   Cable Type
   Single Wire Armour (SWA)
   Armour Clamping
   Two Part Armour Lock
   Sealing Technique
   CMP Unique Displacement Seal Concept
   Sealing Area(s)
   Outer Sheath
   Accessories
   Earth Tag, Serrated Washer, Shroud, Locknut, Adaptor/Reducer, Entry Thread Seal

CMP SOLO Option with LSF Shrouds also available

  Additional Information
   Special Conditions For Safe Use ANZEx 03.3000-0
Open Link
   Special Conditions For Safe Use 01ATEX1286X, 01ATEX3287X
Open Link
 
CMP CWe Type Cable Gland photograph
   
 
CMP CWe Type Cable Gland line diagram
 

Cable Gland Selection Table

       
Gland Size Metric Entry Thread 'C' Minimum Thread Length 'D' Cable Dia 'A' Max Cable Dia 'B' Armour Wire Dia Across Corners Dia 'E' Max Ordering Reference PVC Shroud Ref.
Min Max
20/16 20 15 8.6 6.0 13.4 0.9 24.4 20/16CWe PVC02
20S 20 15 11.6 9.5 15.9 0.9/1.25 26.6 20SCWe PVC04
20 20 15 13.9 12.5 20.9 0.9/1.25 33.3 20CWe PVC06
25 25 15 19.9 17.0 26.2 1.25/1.6 40.5 25CWe PVC09
32 32 15 26.2 22.9 33.9 1.6/2.0 51.0 32CWe PVC11
40 40 15 32.1 26.0 40.4 1.6/2.0 61.0 40CWe PVC15
50S 50 15 38.1 35.0 46.7 2.0/2.5 66.5 50SCWe PVC18
50 50 15 44.0 38.0 53.1 2.0/2.5 78.6 50CWe PVC21
63S 63 15 50.0 45.6 59.4 2.5 83.2 63SCWe PVC23
63 63 15 55.9 54.6 65.9 2.5 89.0 63CWe PVC25
75S 75 15 61.9 57.0 72.1 2.5 101.6 75SCWe PVC28
75 75 15 67.9 60.4 78.5 2.5/3.15 111.1 75CWe PVC30
All dimensions are in millimetres unless otherwise stated
 
 

More information related to these cable glands is available from CMP Products main website.

More info on CMP Products CWe cable gland