A2FRC Cable Gland
CMP Products Cable Gland Main A2FRC Data
CMP产品A2FRC电缆密封接头详细信息介绍

 
A2FRC Flameproof EEx d & Increased Safety EEx e Cable Gland

CMP Type A2FRC Dual Certified Flameproof (Type 'd') and Increased Safety (Type 'e') indoor and outdoor conduit connection cable gland for use in Zone 1, Zone 2, Zone 21 and Zone 22 Hazardous Areas with all types unarmoured cable housed in rigid or flexible conduit system. The cable gland provides a Flameproof seal on the cable outer sheath and is equipped with a rotating female connection for ease of conduit installation.

  Technical Data
   Type
   A2RFC
   Design Specification
   BS 6121:Part 1:1989, EN 50262
   ATEX Certification Detail
   SIRA02ATEX1057X
   ATEX Code of Protection Category
   ATEX Ex II 2 GD EEx d IIC & EEx e II, Equipment Zone 1, Zone 2, Zone 21, & Zone 22 - Gas Groups IIA, IIB, IIC
   EN Compliance Standards
   EN 50014:1997, EN 50018:2000, EN 50019:2000, EN 50281-1-1:1998, IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-1-1
   CEPEL Approval Certificate No.
   Cepel-EX-084/2003X
   NBR Code of Protection Category
   BR-Ex e II
   NBR Compliance Standards
   NBR 9883/95, IEC 60079-0/98
   GOST Ex Certificate
   2002.C256
   GOST Code of Protection Category
   Ex d IIC U / Ex e II U
   GOST Compliance Standards
   GOST P 51330.0-99, GOST P 51330.13-99, GOST P 51330.8-99, GOST P 51330.1-99
   GOST GGTN Permit
   PPC04-6783
   GOST Certificate of Conformity
   5318857
   Lloyds Approval No.
   01/00172
   ABS Approval No.
   01-LD 234401-PDA
   Continuous Operating Temperature
   -60℃ to +130℃
   Ingress Protection Rating
   IP66
   Standard Cable Gland Material
   Brass
   Alternative Cable Gland Material
   Nickel Plated Brass, Aluminium, Stainless Steel
   Seal Material
   CMP SOLO LSF
   Cable Type
   Unarmoured
   Sealing Technique
   CMP Unique Displacement Seal Concept
   Sealing Area(s)
   Outer Sheath
   Accessories
   Entry Thread Seal, Adaptor/Reducer, Serrated Washer, Earth Tag, Shroud, Locknut



  Additional Information
   Special Conditions For Safe Use 02ATEX1057X
Open Link
 
CMP A2FRC Type Cable Gland photograph
   
 
CMP A2FRC Type Cable Gland line diagram
 

Cable Gland Selection Table

     
Gland Size Standard Entry Threads 'B' Minimum Thread Length 'C' + Standard Female NPT Threads Cable Dia 'A' Across Corners Dia 'D' Max Ordering Reference
Metric NPT PG Min Max
20/16 20 1/2" PG11 15 1/2" 3.1 8.6 30.0 20/16A2FRC
20S 20 1/2" PG13.5 15 1/2" 6.1 11.6 30.0 20SA2FRC
20 20 1/2" PG16 15 1/2" 6.5 13.9 30.0 20A2FRC
25 25 3/4" PG21 15 3/4" 11.1 19.9 39.9 25A2FRC
32 32 1" PG29 15 1" 17.0 26.2 45.5 32A2FRC
40 40 1-1/4" PG36 15 1-1/4" 22.0 32.1 55.4 40A2FRC
50S 50 1-1/2" PG36 15 1-1/2" 29.5 38.1 61.0 50SA2FRC
50 50 2" PG42 15 2" 35.6 44.0 72.1 50A2FRC
63S 63 2" PG48 15 2" 40.1 49.9 77.6 63SA2FRC
63 63 2-1/2" - 15 2-1/2" 47.2 55.9 88.7 63A2FRC
75S 75 2-1/2" - 15 2-1/2" 52.8 61.9 88.7 75SA2FRC
75 75 3" - 15 3" 59.1 67.9 105.3 75A2FRC
90 90 3" - 15 3" 66.6 79.3 120.7 90A2FRC
All dimensions are in millimetres unless otherwise stated
 
 